Testing on a second host showed the internal/external split cannot be inferred: iz-pve1's MD1200 sits behind its own HBA while iz-pve0's internal drives sit behind a SAS expander, so the previous "pci-*-scsi-*" glob matched every drive on one host and none on the other. DISK_EXCLUDE_PATTERN now names the shelf's HBA per host. Also fixes parse_disk_limit, which used awk's for-in over split fields and so returned 0 or 70 from "0/70" depending on iteration order. Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
fan_speed
Fan control for Dell PowerEdge servers over IPMI, driven by CPU, GPU and disk temperature, with trend tracking and email alarms.
Upstream (tigerblue77/Dell_iDRAC_fan_controller_Docker) sets fan speed from CPU and GPU only. On a chassis with two dozen drives that misses the thing most likely to be quietly cooking, so this fork adds disks to the curve, records a rolling temperature history, and mails when something looks wrong.
For the MD1200 disk shelf, see the separate md1200-fan-control repo — that enclosure has its own controller and its own serial protocol.
How the fan speed is decided
Each heat source asks for a fan speed and the loudest request wins:
speed = max( interpolate(hottest of CPU/GPU, 45 -> 75),
per-drive interpolation against each drive's own limit )
Sources are never compared as raw temperatures — an 85c CPU and a 45c disk are both
"fine", and a single max() over the numbers would be meaningless.
Why disks are measured against their own limits
Every drive reports its own maximum operating temperature (SATA: Min/Max Temperature Limit; SAS: Drive Trip Temperature). Each drive's ramp is derived from that number:
ramp starts at limit - DISK_RAMP_LOW_OFFSET (default 18)
full speed at limit - DISK_RAMP_HIGH_OFFSET (default 8)
So a Samsung SSD rated to 70c ramps 52→62, and a Toshiba spinner rated to 60c ramps 42→52. The 50c SSD asks for less airflow than the 45c HDD, which is correct — it is further from its own limit.
This matters because temperature does not tell you what you think it does. On these servers the rear-bay SSDs idle 10c hotter than the front-bay spinners: they sit in preheated exhaust air. A shared threshold would peg the fans for drives that are fine and ignore the ones that are not. Measuring each drive against its own envelope makes the curve independent of both drive technology and bay position.
Reported limits are clamped by class. They are not uniformly trustworthy — Samsung
and Kioxia report a real operating maximum (70), Toshiba and Seagate report 60, and WD
Reds report 85, which is the SCT critical limit and not somewhere you want a drive
living. HDD_LIMIT_CAP (60) and SSD_LIMIT_CAP (70) bound whatever the drive claims,
and supply the value when a drive reports nothing.
Drive class comes from /sys/block/<dev>/queue/rotational. That is derived from the
device's RPM flag, which a few SAS drives behind HBAs report incorrectly; if you hit one,
SMART's Rotation Rate field is the fallback.
Alarms
Email via mail to ALERT_EMAIL, which the host's postfix relays. Four conditions:
| Alarm | Fires when |
|---|---|
disk_temp |
A drive is within DISK_ALARM_OFFSET (5c) of its own limit |
trend |
CPU or hottest disk has climbed TREND_RISE_ALARM (8c) across the window while still under every threshold |
smart |
smartctl -H reports anything other than PASSED/OK |
cpu / gpu |
Threshold crossed; cpu also means fan control was handed back to Dell's profile |
disk_count |
Fewer drives answered than were present at startup |
The trend alarm is the one worth having. A dying fan or a blocked intake shows up as a steady climb long before anything crosses a threshold — by the time an absolute alarm fires you have already been running hot for hours.
Every alarm is rate limited per key with a one hour cooldown, and sends a single recovery notice when it clears. On a 10s loop an un-throttled alarm sends 360 emails an hour, at which point the alarm is the outage.
smartctl -H across two dozen drives runs hourly, not per loop. Absolute and trend
checks stay on the fast loop.
Trend history
Every pass appends to log/temps.csv:
epoch,cpu,gpu,hottest_disk,fan_speed
Trimmed to TREND_SAMPLES (90 = 15 minutes at a 10s interval). The trend check compares
the newest sample to the oldest in that window, and reports zero until a full window has
accumulated so a restart cannot alarm on a partial series. Flat file, tail to trim — no
rrdtool, no database.
Usage
fan_speed.sh # the service loop (default)
fan_speed.sh once # a single pass, prints what it decided
fan_speed.sh disks # every drive: temperature and the limit in use
fan_speed.sh selftest # parsers, curve, trend detector, alert rate limiting
selftest touches no hardware and sends no mail — it runs the pure logic against canned
smartctl output and a synthetic history file. Run it after any edit.
Install
install -m 755 fan_speed.sh functions.sh monitor.sh /root/fan_speed/
mkdir -p /root/fan_speed/log /root/fan_speed/state
install -m 644 fan_speed.service /etc/systemd/system/
systemctl daemon-reload
systemctl enable --now fan_speed.service
Tuning
| Variable | Default | |
|---|---|---|
CHECK_INTERVAL |
10 |
Seconds between passes |
LOW_FAN_SPEED / HIGH_FAN_SPEED |
18 / 50 |
Percent |
LOW_TEMPERATURE_THRESHOLD |
45 |
CPU/GPU ramp start |
CPU_TEMPERATURE_THRESHOLD |
90 |
Above this, Dell's profile takes over |
GPU_TEMPERATURE_THRESHOLD |
75 |
|
DISK_RAMP_LOW_OFFSET |
18 |
Ramp starts this far below each drive's limit |
DISK_RAMP_HIGH_OFFSET |
8 |
Full speed this far below it |
DISK_ALARM_OFFSET |
5 |
Alarm this far below it |
HDD_LIMIT_CAP / SSD_LIMIT_CAP |
60 / 70 |
Ceiling on what a drive may claim |
TREND_SAMPLES |
90 |
Window length, in passes |
TREND_RISE_ALARM |
8 |
Degrees of climb that alarms |
DISK_EXCLUDE_PATTERN |
(empty) | by-path substring to skip, e.g. an external shelf's HBA |
ALERT_EMAIL |
Servers@ntfy1.izebra.xyz |
|
ALERT_COOLDOWN |
3600 |
Seconds between repeats of one alarm |
SMART_CHECK_INTERVAL |
3600 |
Seconds between SMART sweeps |
DISK_RAMP_LOW_OFFSET is the knob to reach for first. At the default 18 an SSD rated to
70c starts ramping at 52c; raise the offset to react earlier and louder, lower it to stay
quiet longer. It is set where it is because the hottest drive on iz-pve1 idles at 47c —
close enough that a smaller offset would have the fans tracking normal daily drift, and
you would lose the ability to tell "disks are warm" from "disks are fine".
Those defaults were sized against one chassis. Watch a day of log/temps.csv before
trusting them anywhere else.
Notes
- Kernel device names are not stable — a shelf rescan renamed
sdaa–sdaitosds–sdaamid-session. Everything resolves through/dev/disk/by-pathon every pass; never persist ansdX. - An external shelf must be excluded by hand. Set
DISK_EXCLUDE_PATTERNto its HBA's PCI address in the systemd unit. This cannot be inferred:iz-pve1's MD1200 sits behind its own HBA atpci-0000:04:00.0, whileiz-pve0's internal drives sit behind a SAS expander atpci-0000:02:00.0— so "behind an expander" identifies an external enclosure on one host and the internal backplane on the other.iz-pve1sets it,iz-pve0has no shelf and leaves it empty. - Drive temperature limits are read once at startup. They do not change, and
smartctl -xis far heavier than the-Aused on the fast loop. smartctl -n standbythroughout, so a sleeping drive is skipped rather than spun up just to be measured. That is also whydisk_countalarms on "fewer drives answered" rather than on a device disappearing.
Files
| File | |
|---|---|
fan_speed.sh |
Main loop, fan speed decision, alarm conditions, selftest |
monitor.sh |
Disk reading, trend history, alarm delivery — all local code |
functions.sh |
Vendored upstream: IPMI, iDRAC, interpolation |
fan_speed.service |
systemd unit |