Zeb Hering 80fc40a1ff Alarm on cooling that cannot keep up, not on load
A rising temperature is what a busy machine looks like; the previous
trend alarm would have mailed continuously through a multi-hour zpool
migration. trend_verdict() now alarms only when the fans are already at
maximum and it is still climbing, or when temperature and fan speed are
both rising and the rise is not decelerating.

Tells a plateau from a runaway by comparing the first half of the window
against the second - a load step settles once the fans catch up, a
failing fan does not. Verified quiet against a live migration at load
average 18 with CPU at 68c.

Co-Authored-By: Claude Opus 5 (1M context) <noreply@anthropic.com>
2026-08-28 22:00:17 -07:00

340 lines
13 KiB
Bash

#!/bin/bash
#
# Disk temperature monitoring, trend tracking and email alarms.
#
# Sourced by fan_speed.sh alongside functions.sh. functions.sh is vendored from
# upstream (tigerblue77/Dell_iDRAC_fan_controller_Docker); everything in here is
# local, so keep the two files separate to keep that boundary readable.
# ---------------------------------------------------------------- configuration
DISK_GLOB=${DISK_GLOB:-/dev/disk/by-path/*}
# Drives to leave alone, matched against the by-path link. Set this to the PCI
# address of an external shelf's HBA on any host that has one.
#
# There is no reliable way to infer this. An external enclosure looks exactly
# like an internal backplane from /dev/disk/by-path: iz-pve1's MD1200 sits
# behind its own HBA at pci-0000:04:00.0, while iz-pve0's *internal* drives sit
# behind a SAS expander at pci-0000:02:00.0. Guessing from "-sas-exp" picks up
# the wrong set on one host or the other, so it has to be stated per host.
DISK_EXCLUDE_PATTERN=${DISK_EXCLUDE_PATTERN:-}
# Each drive's fan ramp is derived from its own maximum operating temperature:
# ramp starts at limit - DISK_RAMP_LOW_OFFSET
# full speed at limit - DISK_RAMP_HIGH_OFFSET
# Larger low offset = react earlier = louder. See README before changing.
DISK_RAMP_LOW_OFFSET=${DISK_RAMP_LOW_OFFSET:-18}
DISK_RAMP_HIGH_OFFSET=${DISK_RAMP_HIGH_OFFSET:-8}
# A drive this close to its own limit raises an alarm - the fans are already
# flat out for it and it is still climbing.
#
# That sentence is only true if full fan speed is reached at or before the alarm
# point, i.e. DISK_RAMP_HIGH_OFFSET >= DISK_ALARM_OFFSET. Set the other way round
# the alarm mails you while there is still cooling left unused, which is exactly
# backwards. check_ramp_ordering() enforces it at startup.
DISK_ALARM_OFFSET=${DISK_ALARM_OFFSET:-5}
# True when full cooling is reached no later than the alarm point.
ramp_ordering_ok() {
[ "${1:-$DISK_RAMP_HIGH_OFFSET}" -ge "${2:-$DISK_ALARM_OFFSET}" ]
}
# Clamp rather than refuse to start - a fan controller that exits leaves the
# fans wherever they were, which is worse than a slightly wrong curve.
check_ramp_ordering() {
if ! ramp_ordering_ok; then
echo "/!\\ DISK_RAMP_HIGH_OFFSET ($DISK_RAMP_HIGH_OFFSET) is below DISK_ALARM_OFFSET ($DISK_ALARM_OFFSET):" >&2
echo " the alarm would fire before the fans reach full speed. Raising it to $DISK_ALARM_OFFSET." >&2
log_line "config: raised DISK_RAMP_HIGH_OFFSET $DISK_RAMP_HIGH_OFFSET -> $DISK_ALARM_OFFSET"
DISK_RAMP_HIGH_OFFSET=$DISK_ALARM_OFFSET
fi
}
# Drives report their limit but do not agree on what it means: Samsung and
# Kioxia report a true operating maximum (70), Toshiba and Seagate report 60,
# WD Reds report 85 - the SCT critical limit, not an operating maximum.
# Clamp by class so one optimistic drive cannot quietly disable cooling.
HDD_LIMIT_CAP=${HDD_LIMIT_CAP:-60}
SSD_LIMIT_CAP=${SSD_LIMIT_CAP:-70}
# The fan speed is only pushed to the BMC when it moves by at least this much.
#
# Without it the setpoint is a continuous function of instantaneous temperature:
# the CPU curve is ~1% of fan per degree, idle CPU noise is +/-2c, so the fan
# gets a new speed every single pass and never settles. Measured on iz-pve0,
# stock iDRAC held one speed for 5 minutes straight through the same jitter
# while this script made 7 changes in 16 minutes.
FAN_SPEED_DEADBAND=${FAN_SPEED_DEADBAND:-5}
# Re-push the held speed this often anyway, in case the BMC forgets it. Not
# measured - the MD1200 EMM does forget, iDRAC is believed not to, and one
# ipmitool call every 5 minutes is cheaper than finding out the hard way.
FAN_REASSERT_INTERVAL=${FAN_REASSERT_INTERVAL:-300}
# fan_speed_changed_enough <wanted> <currently applied>
# True when the request has moved far enough to be worth acting on. A request
# for full speed is never held back.
fan_speed_changed_enough() {
local wanted=$1 applied=$2 delta
[ "$wanted" -ge "$HIGH_FAN_SPEED" ] && return 0
delta=$((wanted - applied))
[ "$delta" -lt 0 ] && delta=$((-delta))
[ "$delta" -ge "$FAN_SPEED_DEADBAND" ]
}
# next_fan_speed <wanted> <currently applied> -> the speed to hold from here.
# Kept separate from the re-assert timer on purpose: a re-assert must re-push
# the value already being held, never silently adopt the current request, or
# the deadband leaks a few percent every FAN_REASSERT_INTERVAL.
next_fan_speed() {
local wanted=$1 applied=$2
if [ -z "$applied" ] || fan_speed_changed_enough "$wanted" "$applied"; then
echo "$wanted"
else
echo "$applied"
fi
}
ALERT_EMAIL=${ALERT_EMAIL:-Servers@ntfy1.izebra.xyz}
ALERT_COOLDOWN=${ALERT_COOLDOWN:-3600}
STATE_DIR=${STATE_DIR:-/root/fan_speed/state}
LOG_FILE=${LOG_FILE:-/root/fan_speed/log/fan_speed.log}
TREND_FILE=${TREND_FILE:-/root/fan_speed/log/temps.csv}
TREND_SAMPLES=${TREND_SAMPLES:-90} # 90 x 10s CHECK_INTERVAL = 15 minutes
TREND_RISE_ALARM=${TREND_RISE_ALARM:-8} # degrees of climb across that window
SMART_CHECK_INTERVAL=${SMART_CHECK_INTERVAL:-3600}
# ------------------------------------------------------------------ disk temps
log_line() {
echo "$(date +'%Y-%m-%d %H:%M:%S') || $*" >> "$LOG_FILE"
}
# Block devices behind DISK_GLOB, deduplicated. Resolved fresh every call:
# kernel names are not stable, a shelf rescan renamed sdaa-sdai to sds-sdaa.
disk_devices() {
local link dev
for link in $DISK_GLOB; do
case "$link" in *-part*) continue ;; esac
if [ -n "$DISK_EXCLUDE_PATTERN" ]; then
case "$link" in *"$DISK_EXCLUDE_PATTERN"*) continue ;; esac
fi
[ -e "$link" ] || continue
dev=$(readlink -f "$link")
[ -b "$dev" ] && echo "$dev"
done | sort -u
}
# smartctl -A output on stdin -> temperature in celsius, empty if it did not say.
# Drives disagree on the attribute name: 194 Temperature_Celsius (most),
# 190 Airflow_Temperature_Cel (Seagate), 194 Temperature_Internal (Intel),
# and SCSI/SAS drives report a "Current Drive Temperature" line instead.
# Temperature_Difference_from_100 is a delta, not a reading - never match it.
parse_disk_temperature() {
awk '
/Current Drive Temperature/ { print $4; exit }
/^ *[0-9]+ +[A-Za-z_]*Temperature[A-Za-z_]*/ && !/Difference/ { print $10; exit }'
}
# smartctl -x output on stdin -> the drive's own maximum operating temperature.
parse_disk_limit() {
awk '
/Min\/Max Temperature Limit/ {
if (match($0, /-?[0-9]+\/[0-9]+/)) { split(substr($0, RSTART, RLENGTH), a, "/"); print a[2] }
exit
}
/Drive Trip Temperature/ { print $4; exit }'
}
# -n standby: skip a sleeping drive rather than spinning it up to measure it.
disk_temperature() {
smartctl -n standby -A "$1" 2>/dev/null | parse_disk_temperature
}
# The drive's own limit, clamped by class (see HDD_LIMIT_CAP above).
disk_limit() {
local dev=$1 limit rotational cap
limit=$(smartctl -x "$dev" 2>/dev/null | parse_disk_limit)
rotational=$(cat "/sys/block/$(basename "$dev")/queue/rotational" 2>/dev/null)
if [ "$rotational" = 1 ]; then cap=$HDD_LIMIT_CAP; else cap=$SSD_LIMIT_CAP; fi
if [ -z "$limit" ] || ! [ "$limit" -le "$cap" ] 2>/dev/null; then limit=$cap; fi
echo "$limit"
}
# Limits do not change, and smartctl -x is far heavier than -A. Read them once.
declare -A DISK_LIMIT
cache_disk_limits() {
local dev
DISK_LIMIT=()
for dev in $(disk_devices); do
DISK_LIMIT[$dev]=$(disk_limit "$dev")
done
DISK_COUNT_EXPECTED=${#DISK_LIMIT[@]}
}
# Reads every drive. Sets:
# HOTTEST_DISK_TEMPERATURE / _DEVICE / _LIMIT, DISK_FAN_SPEED, DISKS_READ
# Each drive is interpolated against its OWN limit and the highest resulting fan
# speed wins - so a 50c SSD rated to 70 asks for less than a 45c disk rated to 60.
# That makes the curve independent of drive technology and of bay position.
retrieve_disk_temperatures() {
local dev temp limit speed
HOTTEST_DISK_TEMPERATURE=0
HOTTEST_DISK_DEVICE="-"
HOTTEST_DISK_LIMIT=0
DISK_FAN_SPEED=$LOW_FAN_SPEED
DISKS_READ=0
for dev in $(disk_devices); do
temp=$(disk_temperature "$dev")
[ -n "$temp" ] || continue
DISKS_READ=$((DISKS_READ + 1))
limit=${DISK_LIMIT[$dev]}
[ -n "$limit" ] || limit=$(disk_limit "$dev")
speed=$(calculate_interpolated_fan_speed "$temp" \
$((limit - DISK_RAMP_LOW_OFFSET)) $((limit - DISK_RAMP_HIGH_OFFSET)) \
"$LOW_FAN_SPEED" "$HIGH_FAN_SPEED")
[ "$speed" -gt "$DISK_FAN_SPEED" ] && DISK_FAN_SPEED=$speed
if [ "$temp" -gt "$HOTTEST_DISK_TEMPERATURE" ]; then
HOTTEST_DISK_TEMPERATURE=$temp
HOTTEST_DISK_DEVICE=$dev
HOTTEST_DISK_LIMIT=$limit
fi
done
}
# --------------------------------------------------------------------- alarms
notify() {
local subject=$1 body=$2
if [ -n "$DRY_RUN" ]; then
echo "MAIL[$ALERT_EMAIL] $subject"
else
printf '%s\n' "$body" | mail -s "$subject" "$ALERT_EMAIL"
fi
log_line "ALERT $subject"
}
# raise_alert <key> <subject> <body>
# Rate limited per key. Without this a 10s loop sends 360 mails an hour and the
# alarm becomes the outage.
raise_alert() {
local key=$1 subject=$2 body=$3
local stamp="$STATE_DIR/$key.alert" now last
mkdir -p "$STATE_DIR"
now=$(date +%s)
if [ -f "$stamp" ]; then
last=$(cat "$stamp")
[ $((now - last)) -lt "$ALERT_COOLDOWN" ] && return 0
fi
echo "$now" > "$stamp"
notify "$subject" "$body"
}
# clear_alert <key> <subject> - one recovery notice, only if the alarm was up.
clear_alert() {
local key=$1 subject=$2
local stamp="$STATE_DIR/$key.alert"
[ -f "$stamp" ] || return 0
rm -f "$stamp"
notify "$subject" "Recovered at $(date '+%Y-%m-%d %H:%M:%S')."
}
# ---------------------------------------------------------------------- trend
# record_sample <cpu> <gpu> <disk> <fan>
record_sample() {
mkdir -p "$(dirname "$TREND_FILE")"
echo "$(date +%s),$1,$2,$3,$4" >> "$TREND_FILE"
if [ "$(wc -l < "$TREND_FILE")" -gt $((TREND_SAMPLES * 2)) ]; then
tail -n "$TREND_SAMPLES" "$TREND_FILE" > "$TREND_FILE.tmp" && mv "$TREND_FILE.tmp" "$TREND_FILE"
fi
}
# Is the cooling losing? A rising temperature on its own is not a fault - it is
# what a busy machine looks like, and a zpool migration will do it for hours.
# What matters is whether the fans are answering it:
#
# no_headroom temperature climbing while the fans are already flat out.
# Unambiguous: there is nothing left to give.
# not_converging temperature climbing, fans climbing with it, and the rise is
# not slowing down. Cooling is responding but losing ground.
# quiet anything else, including a big climb that the fans absorbed
# and that has since plateaued. That is just load.
#
# Compares the first half of the window against the second to tell a plateau
# from a runaway - a normal load step decelerates, a cooling failure does not.
#
# trend_verdict <temperature column> <fan column>
trend_verdict() {
local tcol=$1 fcol=$2 lines window oldest mid newest fan_old fan_new first second
lines=$(wc -l < "$TREND_FILE" 2>/dev/null || echo 0)
if [ "$lines" -lt "$TREND_SAMPLES" ]; then echo quiet; return; fi
window=$(tail -n "$TREND_SAMPLES" "$TREND_FILE")
oldest=$(printf '%s\n' "$window" | head -1 | cut -d, -f"$tcol")
mid=$(printf '%s\n' "$window" | sed -n "$(( (TREND_SAMPLES + 1) / 2 ))p" | cut -d, -f"$tcol")
newest=$(printf '%s\n' "$window" | tail -1 | cut -d, -f"$tcol")
fan_old=$(printf '%s\n' "$window" | head -1 | cut -d, -f"$fcol")
fan_new=$(printf '%s\n' "$window" | tail -1 | cut -d, -f"$fcol")
[ -n "$oldest" ] && [ -n "$mid" ] && [ -n "$newest" ] || { echo quiet; return; }
# Not climbing meaningfully - nothing to say either way.
[ $((newest - oldest)) -ge "$TREND_RISE_ALARM" ] || { echo quiet; return; }
# Climbing with the fans already flat out.
if [ "$fan_new" -ge "$HIGH_FAN_SPEED" ]; then echo no_headroom; return; fi
# Climbing, fans climbing too, and the second half of the window rose at least
# as fast as the first - it is not settling.
first=$((mid - oldest))
second=$((newest - mid))
if [ "$fan_new" -gt "$fan_old" ] && [ "$second" -ge "$first" ]; then
echo not_converging; return
fi
echo quiet
}
# rise_over_window <column> -> degrees climbed from the oldest sample in the
# window to the newest. 0 until there is a full window of history, so a restart
# cannot alarm on a partial series. Reported in alarm text; the decision to
# alarm belongs to trend_verdict.
# Columns: 2 cpu, 3 gpu, 4 disk, 5 fan.
rise_over_window() {
local column=$1 oldest newest lines
lines=$(wc -l < "$TREND_FILE" 2>/dev/null || echo 0)
if [ "$lines" -lt "$TREND_SAMPLES" ]; then echo 0; return; fi
oldest=$(tail -n "$TREND_SAMPLES" "$TREND_FILE" | head -1 | cut -d, -f"$column")
newest=$(tail -n 1 "$TREND_FILE" | cut -d, -f"$column")
[ -n "$oldest" ] && [ -n "$newest" ] || { echo 0; return; }
echo $((newest - oldest))
}
# --------------------------------------------------------------- SMART health
# Expensive across two dozen drives - the caller runs this hourly, not per loop.
check_disk_health() {
local dev status failed=""
for dev in $(disk_devices); do
status=$(smartctl -H "$dev" 2>/dev/null | grep -iE "overall-health|SMART Health Status")
[ -n "$status" ] || continue
case "$status" in
*PASSED*|*OK*) ;;
*) failed+="$dev: $status"$'\n' ;;
esac
done
if [ -n "$failed" ]; then
raise_alert smart "SMART failure on $(hostname)" "$failed"
else
clear_alert smart "SMART recovered on $(hostname)"
fi
}